Quick & Helpful Links

 
 

Use the following tables to easily determine the best cooling component for your application.

Material Properties¹

Material  Cp: Specific Heat  p: Density  K: Thermal Conductivity 
BTU/lb°F  J/kg°C  lbs/ft3  kg/m3  BTU/hr ft °F  W/m°C 
AIR (STP) 0.24 1,006 0.07 1.2 0.01 0.017
ALUMINUM, 6061 0.23 896 169 2700 104 180
COPPER, 110 0.09 377 558 8940 226 391
COOLANOL 25 0.44 1,838 56.4 903 0.07 0.12
DIALA-X® 0.44 1,840 54.3 870 0.08 0.14
20/80 EGW SOLUTION 0.93 3,817 63.9 1023 0.33 0.57
40/60 EGW SOLUTION 0.84 3,470 65.7 1052 0.26 0.45
50/50 EGW SOLUTION 0.78 3,283 66.4 1064 0.23 0.39
FLUORINERT®, FC-77 0.25 1,028 110.6 1771 0.036 0.063
HYDRAULIC OIL² 0.44 1,842 54.2 868 0.07 0.12
MIL-H-5606 0.46 1,924 52.5 842 0.08 0.14
MIL-L-23699 0.44 1,830 61.1 980 0.08 0.14
POLYALPHAOLEFIN (PAO) 0.52 2,180 49.6 794 0.08 0.14
SAE 10W OIL 0.45 1,901 54.6 875 0.07 0.12
SAE 30W OIL 0.45 1,901 54.6 875 0.07 0.12
STAINLESS STEEL, 316 0.12 500 501 8025 9.40 16.20
WATER 1.00 4,184 62.3 998 0.34 0.59

¹At 20 °C   ² Typical

Conversion Factors

MULTIPLY BY TO OBTAIN
Watts 3.412 BTU/hr
Watts/°C 1.896 BTU/hr°F
Horsepower 745 Watts
CFM (Cubic Feet per Minute) 0.028 m³/min
PSI (Pounds per Square Inch) 0.069 Bars
PSI (Pounds per Square Inch) 27.68 Inches of Water
GPM (Gallons per Minute) 3.785 LPM (Liters per Minute)
Ft³ (Cubic Feet) 7.48 Gallons
Pressure Head (Feet of Water) 0.434 PSIG
Inches of Water 249 Pascals
In. (Inches) 25.4 mm (millimeters)
lbs (Pounds) 0.454 kg (kilograms)
Tons of Refrigeration 12,000 BTU/Hr
°F (Fahrenheit) 5/9 (°F-32) °C
°C (Celsius) (1.8 x °C)+32 °F
Cp (BTU/lb°F) 4.18 J/kg°C
Density (lb/ft³) 16.018 kg/m³
ΔT (°C) 1.8 ΔT (°F)
Mass Flow (lb/hr) 0.000126 kg/sec

Temperature Conversion

°C °F
-40 -40
-30 -22
-20 -4
-10 14
0 32
10 50
20 68
30 86
40 104
50 122
60 140
70 158
80 176
90 194
100 212
110 230
120 248
130 266
140 284
150 302
160 320
170 338
180 356