Lytron - Total Thermal Solutions
Quick NW Quick NE
 

Cooling Systems

 
Quick NW Quick NE
 

Quick & Helpful Links

 
 
Overview pics Graphs Specs  View:

Recirculating Chiller Kodiak® XT Specifications

Detailed in the two tables below are Lytron's Kodiak XT Chillers specifications. Table one lists specifications for chillers with coolant temperature ranges of -80°C to 90°C and table two lists chillers with ranges of 4°C to 200°C.


Kodiak XT Chiller Models for Low Temperature Operation (-80°C to 90°C)
RC31973G1 RC50106G1 RC50222G1 RC50050G1 RC29246G1
Cooling capacity 550 W at -80°C 1.5 kW at  -80°C 2 kW at  -40°C 500 W at  -40°C 2.5 kW at  -20°C
Temperature stability ±0.5°C (±0.9°F) ±0.5°C (±0.9°F) from -80°C (112°F) to -5°C (23°F), ±3°C (±5.4°F) from -4.9°C (23°F) to 40°C (104°F) ±0.5°C (±0.9°F)
Fluid connections 1/2" Swagelok® Process 1/2" Swagelok®, Facility 3/4" FPT Process 1/2" Swagelok®, Facility 3/4" FPT 1/2" FPT 1/2" FPT
Coolant temperature range -80°C to 50°C
(-121°F to 122°F)
-80°C to 40°C (-112°F to 104°F) - max return temperature of coolant coming back from process is 60°C (140°F) -40°C to 85°C
(-40°F to  185°F)
-40°C to 90°C
(-40°F to 194°F)
-25°C to 90°C
(-13°F to 194°F)
Ambient temperature range 5°C to 30°C
(41°F to 86°F)
5°C to 40°C (41°F to 104°F) 5°C to 40°C
(41°F to 104°F)
5°C to 35°C
(41°F to 95°F)
Dimensions
(W x D x H) in
20.0 x 40.0 x 53.0 20.0 x 40.0 x 64.0 19.3 x 29.0 x 45.8 27.7 x 19.2 x 36.8 19.4 x 27.8 x 38.3
Dimensions
(W x D x H) mm
508 x 1016 x 1346 508 x 1016 x 1626 490.2 x 736.6 x 1163 703.6 x 487.7 x 934.7 492.8 x 706.1 x 972.8
Electrical (Amps) 208-230 V, 3 phase, 60 Hz or 200-220 V, 3 phase, 50 Hz
Pump Type Magnetically coupled gear pump with
VFD and programmable pressure controller
Magnetically coupled turbine pump
Communication RS-485 Remote set point
and retransmission via 0-10 VDC signal
RS-232 9 pin D-sub RS-232 RS232/485
Process Fluid HFE-7100 HFE-7500 Clean water
(≤1 MΩ-cm)/
EGW/PGW
Condenser Air-Cooled Water-Cooled Water-Cooled Air-Cooled Air-Cooled
Compliance Designed to the intent of UL 1995 TUV listed to
UL 1995, build to the intent of
SEMI S2 and F47
CE Certified and MET
Tested to UL 1995
Facility Water
Temperature Range
5°C to 35°C (41°F to 95°F)
Other Features Heater 1.4 kW at 208V Self-contained nitrogen purge (8 mm Swagelok® inlet, 3/8" QD outlet) and anti-siphon kit; Custom interface for fluid fill (1/2" QD); Heater 1700 W at 208V Heater 2 kW at 240V Heater and SS pressurized reservoir
with fill port and air purge
Heater 2 kW at 240V

Kodiak XT Chiller Models for High Temperatures (4°C to 200°C)
RC28125G1 RC50136G1 RC31526G1 RC50112G1
Cooling capacity 4 kW at  20°C (68°F) 33 kW at  20°C (68°F) 7 kW at  20°C (68°F) 800 W at  20°C (68°F)
Temperature stability ±0.5°C (±0.9°F) ±1°C (±1.8°F) ±0.5°C (±0.9°F) ±1°C (±1.8°F)
Fluid connections 1/2" FPT Process and Facilty 1" FPT 1/2" FPT Process 1/2" Swagelok®, Facility 3/4" FPT
Coolant temperature range 5°C to 90°C
(41°F to 194°F)
4°C to 90°C (39°F to 194°F) 10°C to 200°C
(50°F to 392°F)
Ambient temperature range 5°C to 40°C
(41°F to 104°F)
5°C to 35°C (41°F to 95°F)
Dimensions
(W x D x H) in
19.0 x 27.0 x 24.0 32.0 x 60.0 x 45.0 19.2 x 27.7 x 36.8 19.3 x 19.3 x 45.8
Dimensions
(W x D x H) mm
482.6 x 685.8 x 609.6 812.8 x 1524.0 x 1143 487.7 x 703.6 x 934.7 490.2 x 490.2 x 1163.0
Electrical (Amps) 208-230V, 3 phase,, 60 Hz or 200-220V, 3 phase,, 50 Hz 460V, 3 phase,, 60 Hz or 380V, 3 phase,, 50 Hz 208-230V, 3 phase, 60 Hz or 200-220V, 3 phase, 50 Hz
Pump Type Turbine pump Magnetically coupled turbine pump
Communication RS485 25 pin D-sub connector with interlock flow, temp, level, and high/low refrigerant 25 pin D-sub connector with interlock flow, temp and level, DeviceNet
Process Fluid Clean water (≤1 MΩ-cm)/EGW/PGW Baysilone® M 20
Condenser Water-Cooled Air-Cooled Air-Cooled Water-Cooled
Compliance CE Certified and MET tested to UL 1995 CE Certified and MET tested to UL 1995 and SEMI S2/F47 CE Certified and MET tested to UL 1995
Facility Water
Temperature Range
5°C to 35°C
(41°F to 95°F)
5°C to 35°C (41°F to 95°F)
Other Features Heater 2 kW at 240V Heater 4 kW at 240V

To order please call Lytron at +1-781-933-7300.

Get More Information

Complete our short form to request a quote.

 
First Name
Last Name
Company
Email