| First Select Your Model Number |
| |
|
LCS50 |
| Cooling capacity |
|
150 kW (512 kBTU/Hr, 42.6 tons) at 75 GPM (284 LPM) process and 100 GPM (379 LPM) facility flow rates and 10°C (18°F) Initial Temperature Difference (ITD) |
| Temperature stability |
|
±1.0°C (±1.8°F) |
| Fluid connections |
|
2" copper flange terminated at bottom of unit |
| Reservoir capacity |
|
N/A |
| Coolant temperature range |
|
41°F to 95°F/5°C to 35°C |
| Facility water temperature range |
|
39°f to 54°F/4°C to 12°C |
| Ambient temperature range |
|
41°F to 104°F/5°C to 40°C |
| Facility flow rate |
|
25 to 100 gpm/95 to 379 lpm |
| Facility pressure |
|
100 PSI/ 7 bar max |
| Facility pressure drop |
|
See Pressure Drop Graph |
| Physical |
|
|
| Dimensions (W x D x H includes casters) |
inches mm |
24.0 x 48.0 x 76.3 (610 x 1219 x 1938) |
| Weight (empty) |
lbs kg |
900 408 |
| Weight (filled) |
lbs kg |
1017 461 |
| Next, Pick An Electrical Configuration |
| Electrical Configurations and full load amperage (accomodates dual power supply) |
| L01: 208-230 VAC, 3 Phase, 50/60 Hz |
Amps |
18 |
| P01: 460 VAC, 3 Phase, 50/60 Hz |
Amps |
9 |
| Add the Standard DE Pump |
| DE: 3 HP Centrifugal, 2 per system |
x |
| Select Your Controller |
| Controller options |
| Standard Package 3: RS232 controller with digital temperature, flow, and pressure display; modulating valve status reporting; visual alarms for low/high temperature, low flow, pump, power or sensor failure; relay contacts for each alarm; and lock-out protection. |
x |
| Optional Package 4: Package 3 plus visual alarm and relay contacts for dew point; option to control set point based on dew point offset or on fixed temperature with user defined dew point override. |
o |
| Optional Package 5: RS232 and Ethernet controller with digital temperature, flow, and pressure display; modulating valve status reporting; visual alarms for low/high temperature, low flow, pump, power or sensor failure; relay contacts for each alarm; and lock-out protection. |
o |
| Optional Package 6: Package 5 plus visual alarm and relay contacts for dew point; option to control set point based on dew point offset or on fixed temperature with user defined dew point override. |
o |
| Add Any Additional Options |
| Available options (full descriptions of these options can be found below) |
| Internal insulation package |
x |
| 80 mesh coolant filters on process and facility sides |
x |
| FaciDual modulating valves |
x |
| To Arrive At A Part Number |
LCS 50 L01 DE 3 M__ = An LCS 50, 208-230V, 50/60 Hz, with standard DE pump and controller package 3 └A 4 digit option code will be assigned at time of order, based on selected options x = standard o = available option |